DCA-1100SPK

  • Massive 1100 kVA capacity supports critical grid backup
  • Multi-voltage architecture fits complex, large-scale power systems
  • Optimized airflow reduces heat stress during operation
  • Industrial-grade frame endures continuous heavy-load runtime
Quantity
Compare Products

Share to

Specifications Table

Alternator
Frequency (Hz) 50 | 60
Output Rating (kVA) Continuous: 1000 | 1100

Standby: 1100 | 1210

No. of Phases 3-Phase, 4-Wire
Rated Voltage (3) Single Voltage
Power Factor 0.8 (Lagging)
Excitation Brushless, Rotating Exciter (With A.V.R)
Engine
Maker & Model Komatsu SAA12V140
Type Direct Injected, Turbocharged, Aftercooled
Output Rating PS/rpm: 1171/1500 | 1324/1800

kW/rpm: 861/1500 | 974/1800

No. of Cylinders-Bore × Stroke (mm) 12-140×165
Piston Displacement (L) 30.480
Fuel ASTM No.2 Diesel Fuel or Equivalent
Fuel Consumption (L/h) 152 | 169
Lube Oil Sump Capacity (L) 207
Battery x Quantity 145G51 × 4 or 155G51 x 4
Fuel Tank Capacity (L) 600
Unit
Length (mm) 6510 (with visor)
Width (mm) 2200
Height (mm) 2790
Dry Weight (kg) 13000
Sound Level
7m dB (A) 1500/1800 rpm 70 | 74

Compare products

A Quick Glance

Compare key features and find the perfect Denyo machine for your needs.